Technical Information

KVA/AMPERE Data

KVA
Voltage Phase Hz 8 15 30 40 60 80 100 160
110 1 50 72 136 * * * * * *
240 1 50/60 33 62 62 91 137 200 229 366
208 3 50/60 * 41 41 110 166 220 275 444
380 3 50 * 30 41 60 91 120 150 243
415 3 50 * 34 37 55 83 112 140 222
440 3 50/60 * 26 35 52 78 104 130 209
480 3 60 * 24 32 48 72 96 120 192
KVA
Voltage Phase Hz 200 250 350 400 500 850 1000 1250
110 1 50 * * * * * * * *
240 1 50/60 * * * * * * * *
208 3 50/60 555 690 970 1110 1387 * * *
380 3 50 300 380 525 600 759 1290 1519 1899
415 3 50 280 350 490 560 695 1180 1390 1739
440 3 50/60 260 328 455 520 656 115 1312 1640
480 3 50 240 300 420 480 600 1022 1202 1503
Formulae: Three Phase kVA = Volts x Amps x 1.732
  1000
Single Phase kVA = Volts x Amps
  1000

kW = kVA x Power Factor

Cabin and Loading Guidelines

32ft Office Cabin 8kVA Fan Heater 2kW
Toilet/Shower block 10kVA Water Heater 3kW
Mess Room 10kVA Cooker 7kW
Drying Room 10kVA Baby Belling Cooker 3kW
Toilet 5kVA Hand Wash   3kW
  Shower (average)   8kW